Mikoterm TK-24 Professional - Electric boiler (240 kW, 6 bar)
Other variants
- 240 kW for district heating, energy hubs and industry
- Max. working pressure 6 bar, tested to 7 bar
- Modular 10 kW groups
- RS/Modbus-ready for SCADA & EMS integration
- Supports load balancing and peak shaving
- Cascade-ready with redundancy
- Designed for 24/7 critical networks
High-capacity boiler for district heating and industry
The Mikoterm TK-24 Professional (240 kW, 6 bar) is designed for district heating, energy hubs and industrial clusters. With reinforced design and high-pressure capability, it delivers reliable heating under heavy load.
Maximum working pressure and testing
Pressure-tested to 7 bar and certified for 6 bar. Heavy-duty flanges and steel housing ensure safe, long-term use.
Modular output control
240 kW divided into 10 kW groups, switched at 3-second intervals. LCD microprocessor provides accurate temperature settings (10–90 °C).
SCADA and EMS integration
With RS and Modbus connectivity, seamless integration into SCADA and energy management platforms is possible. Enables load balancing and peak shaving within an EMS.
Cascade and redundancy
Cascade-ready for parallel operation of multiple units. Provides scalability and redundancy for critical applications.
Safety and continuous operation
Multi-level safety with continuous pressure and temperature monitoring. Built for 24/7 industrial and district heating environments.
Support from Hewa
Hewa supplies the Mikoterm TK-24 Professional (240 kW, 6 bar) with documentation, Modbus setup and full project support.
| Generals | |
|---|---|
| Item number | 382246 |
| EAN Code | 8606026612443 |
| Sizes ((LxWxH):) | 67 x 61 x 147 cm |
| Specification list | |
| Dimension (W×D×H) mm | 605x665x1470 mm |
| Weight (kg) | 222 kg |
| Water volume in boiler (L) | 165 L |
| Water pipe connection size | G 2 1/2" F |
| Max. concentration of glycol in the medium (%) | 30 % |
| Min. allowable working pressure (software) (bar) | 0.4 bar |
| Max. allowable working pressure (software) (bar) | 6 bar |
| Safety valve (bar) | 7 bar |
| Protection level | IP20 |
| Power supply | 3 Ph - 400/230V 50Hz |
| Power efficiency (%) | 99 % |
| Number of heating elements | 12 |
| Power distribution (kW) | 6 x 40 kW |
| Fuses of the heating elements (A) | 12 x 3p C40 A |
| Compact switch (36kA) with voltage release | 2x Noark Ex9M1S 160A (36kA) |
| Nominal current (A) | 3 x 348 A |
| Recommended main fuses (A) | 3 x 400 A |
| Minimum cross-section of the power cable (mm²) | 3 x 95 mm² (2x) |
| Minimum cross-section of the protective conductor (mm²) | 1 x 35 mm² |
| Temperature range (°C) | 10 - 90 °C |
| Safety thermostat (°C) | 95 °C |
| Microprocessor thermoregulator (CPU) | EK_CPU_1_5 fw: vs15.03.005 |
| Communication with cascade / protocol | RS485_RTU / ModBus |
| Communication with BMS / protocol | RS485_RTU / ModBus |