Mikoterm TK-24 Professional - Electric boiler (180 kW, 6 bar)
Other variants
- 180 kW for district heating, power plants and heavy industry
- Max. working pressure 6 bar, tested up to 7 bar
- Modular 10 kW groups
- RS/Modbus-ready for SCADA & EMS integration
- Cascade-ready with redundancy options
- Designed for peak shaving and load balancing
- 24/7 continuous operation for critical networks
High-capacity heating for district heating and industry
The Mikoterm TK-24 Professional (180 kW, 6 bar) is built for district heating, energy hubs and heavy industrial processes. With 180 kW output and 6 bar pressure rating, it ensures reliable heating even under peak load conditions.
Maximum working pressure and testing
Tested to 7 bar and certified for 6 bar. Reinforced steel housing and flanges guarantee secure operation in high-pressure networks.
Modular power management
180 kW divided into 10 kW groups, switched at 3-second intervals. Microprocessor-controlled LCD enables precise 10–90 °C settings.
SCADA and energy management integration
With RS and Modbus communication, the boiler integrates directly into SCADA and energy management platforms. Perfect for peak shaving and load balancing.
Cascade and redundancy
Cascade-ready for multi-unit operation. Redundancy ensures uninterrupted heating even in case of unit failure.
Safety and 24/7 operation
Multi-level safety system with continuous monitoring of pressure and temperature. Designed for round-the-clock operation in critical infrastructure.
Support from Hewa
Hewa provides the TK-24 Professional (180 kW, 6 bar) with documentation, Modbus setup and full project support.
| Generals | |
|---|---|
| Item number | 384186 |
| EAN Code | 8606026612429 |
| Sizes ((LxWxH):) | 67 x 61 x 147 cm |
| Specification list | |
| Dimension (W×D×H) mm | 605x665x1470 mm |
| Weight (kg) | 208 kg |
| Water volume in boiler (L) | 165 L |
| Water pipe connection size | G 2 1/2" F |
| Max. concentration of glycol in the medium (%) | 30 % |
| Min. allowable working pressure (software) (bar) | 0.4 bar |
| Max. allowable working pressure (software) (bar) | 6 bar |
| Safety valve (bar) | 7 bar |
| Protection level | IP20 |
| Power supply | 3 Ph - 400/230V 50Hz |
| Power efficiency (%) | 99 % |
| Number of heating elements | 9 |
| Power distribution (kW) | 9 x 20 kW |
| Fuses of the heating elements (A) | 9 x 3p C40 A |
| Compact switch (36kA) with voltage release | 2x Noark Ex9M1S 160A (36kA) |
| Nominal current (A) | 3 x 261 A |
| Recommended main fuses (A) | 3 x 300 A |
| Minimum cross-section of the power cable (mm²) | 3 x 50 mm² (2x) |
| Minimum cross-section of the protective conductor (mm²) | 1 x 25 mm² |
| Temperature range (°C) | 10 - 90 °C |
| Safety thermostat (°C) | 95 °C |
| Microprocessor thermoregulator (CPU) | EK_CPU_1_5 fw: vs15.03.005 |
| Communication with cascade / protocol | RS485_RTU / ModBus |
| Communication with BMS / protocol | RS485_RTU / ModBus |