Mikoterm TK-24 Professional - Electric boiler (120 kW, 4 bar)
Other variants
- 120 kW for airports, sports facilities and healthcare centers
- Max. working pressure 4 bar, tested to 4.5 bar
- Modular 10 kW groups, 3-second switching
- RS/Modbus-ready for BMS integration
- Cascade-ready for dynamic demand peaks
- Heavy-duty, powder-coated housing
- Multi-level safety system
Reliable heating for public facilities
The Mikoterm TK-24 Professional (120 kW, 4 bar) is ideal for airports, sports complexes, congress centers and healthcare institutions with fluctuating heat demand. With 120 kW, it delivers stable performance during peaks and base load operation.
Maximum working pressure and testing
Rated for 4 bar, tested to 4.5 bar. Heavy-duty, powder-coated housing ensures long-lasting durability.
Modular output control
120 kW split into 10 kW groups, switched in 3-second intervals. LCD-controlled microprocessor allows precise adjustment (10–90 °C).
Smart connectivity
Equipped with RS and Modbus, the boiler integrates into BMS systems. Dynamic load management optimizes energy use in buildings with varying occupancy.
Cascade operation
Cascade-ready, deployable as a central boiler or in clusters – ideal for facilities with high peak demand.
Safety and reliability
Multi-level safety with continuous monitoring of pressure and temperature. Designed to handle peak loads securely.
Support from Hewa
Hewa supplies the TK-24 Professional (120 kW, 4 bar) with documentation, Modbus setup and project support.
| Generals | |
|---|---|
| Item number | 382124 |
| EAN Code | 8606026610470 |
| Sizes ((LxWxH):) | 67 x 61 x 147 cm |
| Specification list | |
| Dimension (W×D×H) mm | 605x665x1470 mm |
| Weight (kg) | 195 kg |
| Water volume in boiler (L) | 165 L |
| Water pipe connection size | G 2 1/2" F |
| Max. concentration of glycol in the medium (%) | 30 % |
| Min. allowable working pressure (software) (bar) | 0.4 bar |
| Max. allowable working pressure (software) (bar) | 4 bar |
| Safety valve (bar) | 4.5 bar |
| Protection level | IP20 |
| Power supply | 3 Ph - 400/230V 50Hz |
| Power efficiency (%) | 99 % |
| Number of heating elements | 6 |
| Power distribution (kW) | 6 x 20 kW |
| Fuses of the heating elements (A) | 6 x 3p C40 A |
| Compact switch (36kA) with voltage release | 2x Noark Ex9M1S 160A (36kA) |
| Nominal current (A) | 3 x 174 A |
| Recommended main fuses (A) | 3 x 200 A |
| Minimum cross-section of the power cable (mm²) | 3 x 35 mm² (2x) |
| Minimum cross-section of the protective conductor (mm²) | 1 x 16 mm² |
| Temperature range (°C) | 10 - 90 °C |
| Safety thermostat (°C) | 95 °C |
| Microprocessor thermoregulator (CPU) | EK_CPU_1_5 fw: vs15.03.005 |
| Communication with cascade / protocol | RS485_RTU / ModBus |
| Communication with BMS / protocol | RS485_RTU / ModBus |