Mikoterm TK-24 Professional - Electric boiler (120 kW, 6 bar)
Other variants
- 120 kW for chemical, food and industrial processes
- Max. working pressure 6 bar, tested to 7 bar
- Modular 10 kW groups, 3-second switching
- RS/Modbus integration for SCADA systems
- Cascade-ready with redundancy for reliability
- Reinforced heavy-duty design for high-pressure networks
- Built for 24/7 continuous industrial use
Industrial heating solution for critical processes
The Mikoterm TK-24 Professional (120 kW, 6 bar) is designed for demanding industries such as chemical plants, food processing and energy-intensive operations. With reinforced construction and high-pressure capability, it ensures reliable performance in continuous operation.
Maximum working pressure and testing
Pressure-tested up to 7 bar and certified for a maximum working pressure of 6 bar. Ideal for industrial high-pressure networks with strict safety requirements.
Modular power control
120 kW split into 10 kW groups, switched in 3-second intervals. LCD microprocessor provides precise control (10–90 °C, 1 °C increments).
RS and Modbus integration
With RS and Modbus connectivity, the boiler integrates seamlessly into SCADA and energy management platforms. Real-time monitoring and centralized control enhance process security.
Cascade and redundancy
Cascade-ready with redundancy options: even if one unit fails, heating capacity is maintained.
Safety and continuous operation
Multi-level safety system with pressure and temperature monitoring. Engineered for 24/7 process industry use.
Support from Hewa
Hewa provides the TK-24 Professional (120 kW, 6 bar) with full documentation, Modbus setup and engineering support for complex projects.
| Generals | |
|---|---|
| Item number | 382126 |
| EAN Code | 8606026612399 |
| Sizes ((LxWxH):) | 61 x 67 x 147 cm |
| Specification list | |
| Dimension (W×D×H) mm | 605x665x1470 mm |
| Weight (kg) | 200 kg |
| Water volume in boiler (L) | 165 L |
| Water pipe connection size | G 2 1/2" F |
| Max. concentration of glycol in the medium (%) | 30 % |
| Min. allowable working pressure (software) (bar) | 0.4 bar |
| Max. allowable working pressure (software) (bar) | 6 bar |
| Safety valve (bar) | 7 bar |
| Protection level | IP20 |
| Power supply | 3 Ph - 400/230V 50Hz |
| Power efficiency (%) | 99 % |
| Number of heating elements | 6 |
| Power distribution (kW) | 6 x 20 kW |
| Fuses of the heating elements (A) | 6 x 3p C40 A |
| Compact switch (36kA) with voltage release | 2x Noark Ex9M1S 160A (36kA) |
| Nominal current (A) | 3 x 174 A |
| Recommended main fuses (A) | 3 x 200 A |
| Minimum cross-section of the power cable (mm²) | 3 x 35 mm² (2x) |
| Minimum cross-section of the protective conductor (mm²) | 1 x 16 mm² |
| Temperature range (°C) | 10 - 90 °C |
| Safety thermostat (°C) | 95 °C |
| Microprocessor thermoregulator (CPU) | EK_CPU_1_5 fw: vs15.03.005 |
| Communication with cascade / protocol | RS485_RTU / ModBus |
| Communication with BMS / protocol | RS485_RTU / ModBus |