Mikoterm TK-24 Professional - Electric boiler (160 kW, 4 bar)
Other variants
- 160 kW for stadiums, hospitals and campuses
- Max. working pressure 4 bar, tested to 4.5 bar
- Modular 10 kW groups
- RS/Modbus-ready for BMS integration
- Cascade-ready for large buildings
- Suitable for hot water and space heating
- Multi-level safety system
High-capacity heating for large facilities
The Mikoterm TK-24 Professional (160 kW, 4 bar) is designed for facilities with extremely high heat demand, such as stadiums, hospitals, campuses and swimming pools. With 160 kW output, it provides reliable heating for both space and hot water.
Maximum working pressure and testing
Rated for 4 bar and tested to 4.5 bar. Heavy-duty steel housing with powder coating ensures long-lasting durability.
Modular output management
160 kW split into 10 kW groups, switched at 3-second intervals. This modular system avoids peak loads and increases efficiency.
Smart connectivity
With RS and Modbus connectivity, integration into BMS is simple. Load balancing and dynamic control optimize energy use even during peak demand.
Cascade and scalability
Cascade-ready, usable as a central boiler or in clusters. Ideal for projects with expanding heating needs.
Safety and reliability
Multi-level safety system with pressure and temperature monitoring. Stable performance even under peak loads.
Support from Hewa
Hewa provides the TK-24 Professional (160 kW, 4 bar) with documentation, Modbus setup and project support.
| Generals | |
|---|---|
| Item number | 382164 |
| EAN Code | 8606026610494 |
| Sizes ((LxWxH):) | 67 x 61 x 147 cm |
| Specification list | |
| Dimension (W×D×H) mm | 605x665x1470 mm |
| Weight (kg) | 205 kg |
| Water volume in boiler (L) | 165 L |
| Water pipe connection size | G 2 1/2" F |
| Max. concentration of glycol in the medium (%) | 30 % |
| Min. allowable working pressure (software) (bar) | 0.4 bar |
| Max. allowable working pressure (software) (bar) | 4 bar |
| Safety valve (bar) | 4.5 bar |
| Protection level | IP20 |
| Power supply | 3 Ph - 400/230V 50Hz |
| Power efficiency (%) | 99 % |
| Number of heating elements | 8 |
| Power distribution (kW) | 8 x 20 kW |
| Fuses of the heating elements (A) | 8 x 3p C40 A |
| Compact switch (36kA) with voltage release | 2x Noark Ex9M1S 160A (36kA) |
| Nominal current (A) | 3 x 232 A |
| Recommended main fuses (A) | 3 x 250 A |
| Minimum cross-section of the power cable (mm²) | 3 x 50 mm² (2x) |
| Minimum cross-section of the protective conductor (mm²) | 1 x 25 mm² |
| Temperature range (°C) | 10 - 90 °C |
| Safety thermostat (°C) | 95 °C |
| Microprocessor thermoregulator (CPU) | EK_CPU_1_5 fw: vs15.03.005 |
| Communication with cascade / protocol | RS485_RTU / ModBus |
| Communication with BMS / protocol | RS485_RTU / ModBus |